Technical sheet
Description
Industrial Ethernet Cat.7 4x2xAWG22-100 FC FR-PvC GN c(UL)us CMG
Application
PROFINET compliant, for fixed installation using fast connect design
Conductor
Bare copper wire AWG22, 7-stranded
tinned copper wires AWG23 or 7-stranded bare copper wires AWG26
Insulation
Foam-skin polyolefin
Core identification
colour coded in accordence with IEC 60708
1° shield/armouring
Plastic bonded aluminium tape, tinned drain wire (optional)
Inner jacket/tape
Plastic tape and extruded covering (optional)
2° shield/armouring
Braid of tinned copper wires
Jacket colour
green similar to RAL 6018
Operating temperature
-40°C to +80°C fixed installation
Operating voltage
max. 125 v (peak value,
not for connection to public mains)
Impedance
nom. 100 ohm according to IEC 61156-5
(AWG22) or IEC 61156-6 (AWG23 and AWG26)
Resistance
max. 115.0 ohm / km (AWG22)
max. 146.2 ohm / km (AWG23)
max. 280.0 ohm / km (AWG26)
Nominal capacity
nom. 48 nF/Km
Bending Radius
8 x cable diameter fixed installation
Approvals / norms
c(UL)us listing CMG according to UL 444