ethernetbus

PROFIBUS DP/FMS/FIP

(IM-110630)

PROFIBUS DP/FMS/FIP
Technical sheet
Description
PROFIBUS DP flex 1x2x0.64L-150+3x1.0 FR-PVC violet DESINA c(UR)us AWM
Application
for fixed installation and flexible application without compulsory guide for connection to Siemens ET 200C with integrated power supply using standard cable design
Conductor
Data pairs: Bare copper wire, diameter: 0.64mm approx AWG22
or 7-stranded bare copper wires AWG24 Power supply cores: Stranded bare copper wires 1.0 mm²
Core numbers
5
Stranding
1x2x0,64 mm²+3x1 mm²
Section
0,64 mm², 1 mm²
Insulation
Data pairs: Foam-skin polyolefin (red and green)
Power supply cores: Polyolefin
(colour coded in accordence with DIN VDE 0293)
Core identification
Data pairs: red and green
Power supply cores: colour coded in accordance with DIN VDE 0293
1° shield/armouring
Plastic bonded aluminium tape, braid of tinned copper wires
Inner jacket/tape
Plastic tape and / or extruded covering (fast connect design)
Outer jacket
PVC
Jacket colour
violet similar to RAL 4001
Outer diameter mm.
9,8
Cu weight Kg/Km
60
Cable weight Kg/Km
108
Operating temperature
-40°C to +80°C fixed installation
-40°C to +70°C fixed installation (PE)
-25°C to +80°C fixed installation (FRNC)
-40°C to +105°C fixed installation (PROFIBUS DP Extemp)
-10°C to +70°C flexible application (only flexible designs)
Operating voltage
max. 250 V (peak value, not for connection to public mains)
Impedance
150 ± 15 ohm
Resistance
max. 110.0 ohm / km (solid conductor)
max. 175.2 ohm / km (7-stranded conductor)
max. 39.0 ohm / km (power supply)
Nominal capacity
max. 30 nF/Km
Bending Radius
8 x cable diameter fixed installation
15 x cable diameter flexible application (only flexible design)
Approvals / norms
approval c(UL)us recognized AWM style 2464 60° 300V, IEC 60332-1-2, Cable flame test (UL 2556)