Technical sheet
Description
PROFIBUS DP 1x2x0.64-150 FR-PVC violet DESINA
Application
for fixed installation using standard cable design
Conductor
Data pairs: Bare copper wire, diameter: 0.64mm approx AWG22
or 7-stranded bare copper wires AWG24 Power supply cores: Stranded bare copper wires 1.0 mm²
Insulation
Data pairs: Foam-skin polyolefin (red and green)
Power supply cores: Polyolefin
(colour coded in accordence with DIN VDE 0293)
Core identification
Data pairs: red and green
Power supply cores: colour coded in accordance with DIN VDE 0293
1° shield/armouring
Plastic bonded aluminium tape, braid of tinned copper wires
Inner jacket/tape
Plastic tape and / or extruded covering
(fast connect design)
Jacket colour
violet similar to RAL 4001
Operating temperature
-40°C to +80°C fixed installation
-40°C to +70°C fixed installation (PE)
-25°C to +80°C fixed installation (FRNC)
-40°C to +105°C fixed installation (PROFIBUS DP Extemp)
-10°C to +70°C flexible application (only flexible designs)
Operating voltage
max. 250 V (peak value,
not for connection to public mains)
Resistance
max. 110.0 ohm / km (solid conductor)
max. 175.2 ohm / km (7-stranded conductor)
max. 39.0 ohm / km (power supply)
Nominal capacity
max. 30 nF/Km
Bending Radius
8 x cable diameter fixed installation
10 x cable diameter flexible application
Approvals / norms
c(UR)us recognition AWM style 2464 (80°C, 300V) according to UL 758, IEC 60332-1-2
VW-1 (UL 2556)